What an earth-resistance reading proves on a small install
The rod reading is not the loop. An ohm on PEN is not protection.
Listen to the post
The browser's own voice. Code and figures are skipped.
Earth-electrode resistance is the rod into the soil. It is not loop impedance. It is not the residual-current trip time.
A small flat or shop often has one rod, one clamp, one sheet of paper. 10 Ω or 20 Ω — whichever the rule asks for. The number talks about the soil around that rod. It does not talk about the protective conductor, joint continuity, or neutral-to-earth voltage.
On TN-C-S (PEN split) personal protection comes from the residual-current device and from the loop. A rod, if there is one, is a different job: equipotential, lightning, a leak path. Bonding PEN to a rod and calling it “earthed” does not save the device or the loop.
Measure: three-pole or clamp, at the joint. Paint, rust, and a loose clamp are not a reading. Continuity is a different instrument and a different protocol.
If there is no rod and the supply is TN-S / TN-C-S, the electrode reading is not invented. A thing that is not there is not written down as 0.8 Ω.