What a 30 mA RCD actually opens in a small installation

Personal protection, a mixed neutral, and what the test button does not prove.

Listen to the post

The browser's own voice. Code and figures are skipped.

30 mA is not a fire device. It is for a person. 300 mA is the fire job, and it is a different one.

A small flat or shop board usually has a C-curve breaker at the incomer and a 30 mA residual-current device next to it. If there is a wet room, putting that circuit on its own 30 mA is less stupid than hanging the whole dwelling off one.

The device watches the difference between the current in the line and the current in the neutral. Difference means current is leaving on the protective conductor or through earth. Bond neutral to protective earth on the load side of the device and it sees a standing difference. It opens on first energisation. The device is not faulty. The joint is.

The test button makes a small difference through the device’s own shunt. If it opens, the mechanism is alive. It does not measure earth resistance, loop impedance, or the real leakage path. Press it monthly. If it does not open, replace the device. Do not “try again later”.

A shared neutral — two devices, one neutral — nuisance-trips on the first uneven load. Each device keeps its own neutral.

On a TN-C (PEN) supply, 30 mA personal protection does not work cleanly. Fitting the device without splitting PEN to TN-C-S exists on paper. On site it does not.

Measure: loop impedance, trip time, residual threshold. The test button is not that list.